- Home
- Loading
| Item ID |
|---|
| Title |


| Ratings per : | IEC/EN 60947-7-3 |
| Ratings (note) : | Electrical ratings are given by the fuse and blown fuse indication. |
| Nominal voltage (III/3) : | 250 V |
| Ratings per : | IEC/EN 60947-7-3 |
| Ratings (note) : | Electrical ratings are given by the fuse and blown fuse indication. |
| Nominal voltage (III/3) : | 250 V |
| Processing temperature : | -35 … +85 °C |
| Continuous operating temperature : | -60 … +105 °C |
| Width : | 6.2 mm / 0.244 inches |
| Height : | 66.1 mm / 2.602 inches |
| Depth from upper-edge of DIN-rail : | 57.6 mm / 2.268 inches |
| Note (material data) : | <a href="https://www.wago.com/us/material-specifications" href="_blank">Information on material specifications can be found here</a> |
| Color : | Gray |
| Material group : | I |
| Mounting type : | DIN-35 rail |
| Marking level : | Center/side marking |
| Fuse receptacle : | Pivoting |
| Fuse type : | Cylindrical fuse; 5 x 20 mm |
| Product Group Code : | 0036 |
| Packaging type : | Box |
| Country of origin : | DE |
| GTIN : | 4055143907934 |
| Reference hazardous areas : | See “Downloads – Documentation – Additional Information: Technical Section; Technical Explications” |
| Ratings per : | ATEX: PTB 20 ATEX 1007 U / IECEx: PTB 20.0013U (Ex ec IIC Gc) |
| Rated voltage EN (Ex e II) : | 275 V |
| Approvals per : | CSA 22.2 No 158 |
| Rated voltage CSA (Use Group B) : | 250 V |
| Rated current CSA (Use Group B) : | 10 A |
| Power loss (max.) Pl (max.) (note) : | When selecting glass cartridge fuses, make sure that the maximum power loss listed below is not exceeded. The power loss is determined according to IEC or EN 60947-7-3/VDE 0611-6 at 23°C. The temperature rise of the terminal block must be checked according to their application and mounting. Higher ambient temperatures represent an additional impact on miniature fuses. Therefore, in such applications, the rated current must be reduced if necessary. More details are available from the manufacturers. |
| Power loss Pl max. overload and short-circuit protection (individual arrangement) : | 1.6 W |
| Power loss Pl max. overload and short-circuit protection (group arrangement) : | 1.6 W |
| Connection technology : | Push-in CAGE CLAMP® |
| Actuation type : | Push-button |
| Connectable conductor materials : | Copper |
| Approvals per : | UL 1059 |
| Rated voltage UL (Use Group B) : | 250 V |
| Rated current UL (Use Group B) : | 10 A |