| Product Certifications : | cULus || CE || UKCA || DNV-GL || ABS || LR |
| Resistance To Conducted Disturbances : | 10 V 0.15...80 MHz IEC 61000-4-6 || 3 V 0.1...80 MHz Marine specification (LR, ABS, DNV, GL) || 10 V spot frequency (2, 3, 4, 6.2, 8.2, 12.6, 16.5, 18.8, 22, 25 MHz) Marine specification (LR, ABS, DNV, GL) |
| Resistance To Electromagnetic Fields : | 10 V/m 80 MHz...1 GHz IEC 61000-4-3 || 3 V/m 1.4 GHz...2 GHz IEC 61000-4-3 || 1 V/m 2 GHz...3 GHz IEC 61000-4-3 |
| Immunity To Microbreaks : | 10 ms |
| Storage Altitude : | 0-3000 m |
| Standards : | ANSI/ISA 12-12-01 || CSA C22.2 No 142 || CSA C22.2 No 213 || IEC 61131-2:2007 || Marine specification (LR, ABS, DNV, GL) || UL 508 |
| Pollution Degree : | 2 |
| Ambient Air Temperature For Operation : | -10-35 °C vertical installation) || -10-55 °C horizontal installation) |
| Shock Resistance : | 15 gn 11 ms |
| Vibration Resistance : | 3.5 mm 5-8.4 Hz symmetrical rail || 3 gn 8.4-150 Hz symmetrical rail || 3.5 mm 5-8.4 Hz panel mounting || 3 gn 8.4-150 Hz panel mounting |
| Ambient Air Temperature For Storage : | -25-70 °C |
| Relative Humidity : | 10-95 %, without condensation in operation) || 10-95 %, without condensation in storage) |
| Ip Degree Of Protection : | IP20 with protective cover in place |
| Resistance To Electrostatic Discharge : | 8 kV in air IEC 61000-4-2 || 4 kV on contact IEC 61000-4-2 |
| Resistance To Fast Transients : | 2 kV IEC 61000-4-4 power lines) || 1 kV IEC 61000-4-4 Ethernet line) || 1 kV IEC 61000-4-4 serial link) |
| Operating Altitude : | 0...2000 m |
| Electromagnetic Emission : | conducted emissions 120...69 dBµV/m QP power lines)10-150 kHz IEC 55011 || conducted emissions 63 dBμV/m QP power lines)1.5-30 MHz IEC 55011 || radiated emissions 40 dBμV/m QP class A 10 m)30-230 MHz IEC 55011 || conducted emissions 79...63 dBμV/m QP power lines)150-1500 kHz IEC 55011 || radiated emissions 47 dBμV/m QP class A 10 m)230-1000 MHz IEC 55011 |